The New IS:12615-2011 is based on the International Standard IEC 60034-30 (2008) which defines New Efficiency Classification for single speed, three phase, induction motors.
The IS:12615-2011 covers single speed, three-phase, 50Hz, cage induction motors that:
• have rated voltage ≤1000V;
• have a rated output 0.37kW ≤ PN ≤ 375kW;
• have either 2, 4 or 6 poles;
• meet frame size to output relation as stipulated in IS:1231 (for outputs covered by IS:1231);
• are rated on the basis of either duty type S1 (continuous duty) or S3 (intermittent periodic duty) with rated cyclic duration factor of 80% or higher;
• are capable of operating direct on-line;
• are designed for operation on virtually sinusoidal and balanced voltage conditions as defined in 7.2.1 of IS/IEC 60034-1;
• designed for an ambient temperature not exceeding 40°C and altitude not exceeding 1000m;
• have degree of protection IP44 or superior;
• have method of cooling IC411 in accordance with IS 6362 / IEC 60034-6;
• have service factor not exceeding 1.0.

The Efficiency classes defined are:
IE1 - Standard Efficiency
IE2 - High Efficiency
IE3 - Premium Efficiency

The values of efficiency for motors to classify as IE2 or IE3 in accordance with the new IS:12615-2011 are as under:



kW2 Pole4 Pole6 Pole
Frame SizeEfficiency %Frame SizeEfficiency %Frame SizeEfficiency %
IE2IE3IE2IE3IE2IE3
0.377172.275.57170.173806971.9
0.557174.878.18075.1788072.975.9
0.758077.480.78079.682.590S75.978.9
1.18079.682.790S81.484.190L78.181
1.590S81.384.290L82.885.3100L79.882.5
2.290L83.285.9100L84.386.7112M81.884.3
3.7100L85.587.8112M86.388.4132S84.386.5
5.5132S8789.2132S87.789.6132M8688
7.5132S88.190.1132M88.790.4160M87.289.1
11160M89.491.2160M89.891.4160L88.790.3
15160M90.391.9160L90.692.1180L89.791.2
18.5160L90.992.4180M91.292.6200L90.491.7
22180M91.392.7180L91.693200L90.992.2
30200L9293.3200L92.393.6225M91.792.9
37200L92.593.7225S92.793.9250M92.293.3
45225M92.994225M93.194.2280S92.793.7
55250M93.294.3250M93.594.6280M93.194.1
75280S93.894.7280S9495315S93.794.6
90280M94.195280M94.295.2315M9494.9
110315S94.395.2315S94.595.4315M#94.395.1
125315M94.595.3315M94.695.5315M#94.495.2
132315M#94.695.4315M#94.795.6315L#94.695.4
160315L#94.895.6315L#94.995.8355L94.895.6
200315L9595.8315L95.196355L9595.8
250355L9595.8355L95.196355L9595.8
315355L9595.8355L95.1969595.8
3759595.895.1969595.8